A perfectly sealed and insulated building would hold heat for ever and thus would need no heating. The two dominant reasons why buildings lose heat are:
In the standard model for heat loss, both these heat flows are proportional to the temperature difference between the air inside and outside. For a typical British house, conduction is the bigger of the two losses, as we’ll see.
Conduction loss
The rate of conduction of heat through a wall, ceiling, floor, or window is the product of three things: the area of the wall, a measure of conductivity of the wall known in the trade as the “U-value” or thermal transmittance, and the temperature difference –
The U-value is usually measured in
The U-values of objects that are “in series,” such as a wall and its inner lining, can be combined in the same way that electrical conductances combine:
There’s a worked example using this rule.
Ventilation loss
To work out the heat required to warm up incoming cold air, we need the heat capacity of air:
In the building trade, it’s conventional to describe the power-losses caused by ventilation of a space as the product of the number of changes
| kitchen | 2 |
|---|---|
| bathroom | 2 |
| lounge | 1 |
| bedroom | 0.5 |
Air changes per hour: typical values of
|
U-values |
|||
|---|---|---|---|
| old buildings | modern standards | best methods | |
| Walls | 0.45-0.6 | 0.12 | |
| solid masonry wall | 2.4 | ||
| outer wall: 9 inch solid brick | 2.2 | ||
| 11 inch brick-block cavity wall, unfilled | 1.0 | ||
| 11 inch brick-block cavity wall, insulated | 0.6 | ||
| Floors | 0.45 | 0.14 | |
| suspended timber floor | 0.7 | ||
| solid concrete floor | 0.8 | ||
| Roofs | 0.25 | 0.12 | |
| flat roof with 25 mm insulation | 0.9 | ||
| pitched roof with 100 mm insulation | 0.3 | ||
| Windows | 1.5 | ||
| single-glazed | 5.0 | ||
| double-glazed | 2.9 | ||
| double-glazed, 20 mm gap | 1.7 | ||
| triple-glazed | 0.7-0.9 |
U-values of walls, floors, roofs, and windows.
Energy loss and temperature demand (degree-days)
Since energy is power
and the energy lost by ventilation as
Both these energy losses have the form
Figure E.3: U-values required by British and Swedish building regulations.
where the “Something” is measured in watts per
The first factor is a property of the building measured in watts per
Figure E.4: The temperature demand in Cambridge, 2006, visualized as an area on a graph of daily average temperatures. (a) Thermostat set to
We can reduce our energy loss by reducing the leakiness of the building, or by reducing our temperature demand, or both. The next two sections look more closely at these two factors, using a house in Cambridge as a case-study.
There is a third factor we must also discuss. The lost energy is replenished by the building’s heating system, and by other sources of energy such as the occupants, their gadgets, their cookers, and the sun. Focussing on the heating system, the energy delivered by the heating is not the same as the energy consumed by the heating. They are related by the coefficient of performance of the heating system.
For a condensing boiler burning natural gas, for example, the coefficient of performance is 90%, because 10% of the energy is lost up the chimney.
Figure E.5: Temperature demand in Cambridge, in degree-days per year, as a function of thermostat setting
To summarise, we can reduce the energy consumption of a building in three ways:
We now quantify the potential of these options. (A fourth option – increasing the building’s incidental heat gains, especially from the sun – may also be useful, but I won’t address it here.)
Temperature demand
We can visualize the temperature demand nicely on a graph of external temperature versus time (figure E.4). For a building held at a temperature of
Figure E.6: The temperature demand in Cambridge, 2006, replotted in units of degree-days per day, also known as degrees. In these units, the temperature demand is just the average of the temperature difference between inside and outside.
These calculations give us a ballpark indication of the benefit of turning down thermostats, but will give an exact prediction only if we take into account two details: first, buildings naturally absorb energy from the sun, boosting the inside above the outside temperature, even without any heating; and second, the occupants and their gadget companions emit heat, so further cutting down the artificial heating requirements. The temperature demand of a location, as conventionally expressed in degree-days, is a bit of an unwieldy thing. I find it hard to remember numbers like “3500degree-days.” And academics may find the degree-day a distressing unit, since they already have another meaning for degree days (one involving dressing up in gowns and mortar boards). We can make this quantity more meaningful and perhaps easier to work with by dividing it by 365, the number of days in the year, obtaining the temperature demand in “degree-days per day,” or, if you prefer, in plain “degrees.” Figure E.6 shows this replotted temperature demand. Expressed this way, the temperature demand is simply the average temperature difference between inside and outside. The highlighted temperature demands are:
Leakiness – example: my house
My house is a three-bedroom semi-detached house built about 1940 (figure E.7). By 2006, its kitchen had been slightly extended, and most of the windows were double-glazed. The front door and back door were both still single-glazed.
My estimate of the leakiness in 2006 is built up as shown in table. The total leakiness of the house was
Figure E.7: My house.
| Conductive leakiness |
area |
U-value |
leakiness |
|---|---|---|---|
| Horizontal surfaces | |||
| Pitched roof | 48 | 0.6 | 28.8 |
| Flat roof | 1.6 | 3 | 4.8 |
| Floor | 50 | 0.8 | 40 |
| Vertical surfaces | |||
| Extension walls | 24.1 | 0.6 | 14.5 |
| Main walls | 50 | 1 | 50 |
| Thin wall (5in) | 2 | 3 | 6 |
| Single-glazed doors and windows | 7.35 | 5 | 36.7 |
| Double-glazed windows | 17.8 | 2.9 | 51.6 |
| Total conductive leakiness | 232.4 |
| Ventilation leakiness |
volume |
|
leakiness |
|---|---|---|---|
| Bedrooms | 80 | 0.5 | 13.3 |
| Kitchen | 36 | 2 | 24 |
| Hall | 27 | 3 | 27 |
| Other rooms | 77 | 1 | 25.7 |
| Total ventilation leakiness | 90 |
Breakdown of my house’s conductive leakiness, and its ventilation leakiness, pre-2006. I’ve treated the central wall of the semi-detached house as a perfect insulating wall, but this may be wrong if the gap between the adjacent houses is actually well-ventilated.
I’ve highlighted the parameters that I altered after 2006, in modifications to be described shortly.
To compare the leakinesses of two buildings that have different floor areas, we can divide the leakiness by the floor area; this gives the heat-loss parameter of the building, which is measured in
Let’s use these figures to estimate the house’s daily energy consumption on a cold winter’s day, and year-round.
On a cold day, assuming an external temperature of
If the temperature is maintained at
To get a year-round heat-loss figure, we can take the temperature demand of Cambridge from figure E.5. With the thermostat at
Turning the thermostat down to
Effects of extra insulation
During 2007, I made the following modifications to the house:
What’s the predicted change in heat loss?
The total leakiness before the changes was
Adding cavity-wall insulation (new U-value 0.6) to the main walls reduces the house’s leakiness by
The heat-loss parameter of this house (total floor area
| Cavity-wall insulation (applicable to two-thirds of the wall area) | 4.8 kWh/d |
|---|---|
| – Improved roof insulation | 3.5 kWh/d |
| – Reduction in conduction from double-glazing two doors and one window | 1.9 kWh/d |
| – Ventilation reductions in hall and kitchen from improvements to doors and windows | 2.9 kWh/d |
Break-down of the predicted reductions in heat loss from my house, on a cold winter day.
It’s frustratingly hard to make a really big dent in the leakiness of an already-built house! As we saw a moment ago, a much easier way of achieving a big dent in heat loss is to turn the thermostat down. Turning down from 20 to
Combining these two actions – the physical modifications and the turning-down of the thermostat – this model predicts that heat loss should be reduced by nearly 50%. Since some heat is generated in a house by sunshine, gadgets, and humans, the reduction in gas consumption should be more than 50%.
I made all these changes to my house and monitored my meters every week. I can confirm that my heating bill indeed went down by more than 50%. As figure 21.4 showed, my gas consumption has gone down from 40 kWh/d to 13 kWh/d – a reduction of 67%.
Leakiness reduction by internal wall-coverings
Can you reduce your walls’ leakiness by covering the inside of the wall with insulation? The answer is yes, but there may be two complications. First, the thickness of internal covering is bigger than you might expect. To transform an existing nine-inch solid brick wall (U-value
If you’re not looking for such a big reduction in wall leakiness, you can get by with a thinner internal covering. For example, you can buy 1.8-cm-thick insulated wallboards with a U-value of
Definitely a worthwhile reduction.
Air-exchange
Once a building is really well insulated, the principal loss of heat will be through ventilation (air changes) rather than through conduction. The heat loss through ventilation can be reduced by transferring the heat from the outgoing air to the incoming air. Remarkably, a great deal of this heat can indeed be transferred without any additional energy being required. The trick is to use a nose, as discovered by natural selection. A nose warms incoming air by cooling down outgoing air. There’s a temperature gradient along the nose; the walls of a nose are coldest near the nostrils. The longer your nose, the better it works as a counter-current heat exchanger. In nature’s noses, the direction of the air-flow usually alternates. Another way to organize a nose is to have two air-passages, one for in-flow and one for out-flow, separate from the point of view of air, but tightly coupled with each other so that heat can easily flow between the two passages. This is how the noses work in buildings. It’s conventional to call these noses heat-exchangers.
An energy-efficient house
In 1984, an energy consultant, Alan Foster, built an energy-efficient house near Cambridge; he kindly gave me his thorough measurements. The house is a timber-framed bungalow based on a Scandinavian “Heatkeeper Serrekunda” design (figure E.10), with a floor area of
Figure E.10: The Heatkeeper Serrekunda.
The walls are 30 cm thick and have a U-value of
The house is well sealed, every door and window lined with neoprene gaskets. The house is heated by warm air pumped through floor grilles; in winter, pumps remove used air from several rooms, exhausting it to the outside, and they take in air from the loft space. The incoming air and outgoing air pass through a heat exchanger (figure E.11), which saves 60% of the heat in the extracted air. The heat exchanger is a passive device, using no energy: it’s like a big metal nose, warming the incoming air with the outgoing air. On a cold winter’s day, the outside air temperature was
Figure E.11: The Heatkeeper’s heat-exchanger.
For the first decade, the heat was supplied entirely by electric heaters, heating a 150-gallon heat store during the overnight economy period. More recently a gas supply was brought to the house, and the space heating is now obtained from a condensing boiler.
The heat loss through conduction and ventilation is
With the house occupied by two people, the average space-heating consumption, with the thermostat set at 19 or
Figure E.12 compares the power consumption per unit area of this Heatkeeper house with my house (before and after my efficiency push) and with the European average. My house’s post-efficiency-push consumption is close to that of the Heatkeeper, thanks to the adoption of lower thermostat settings.
Benchmarks for houses and offices
The German Passivhaus standard aims for power consumption for heating and cooling of
The average energy consumption of the UK service sector, per unit floor area, is
An energy-efficient office
The National Energy Foundation built themselves a low-cost low-energy building. It has solar panels for hot water, solar photovoltaic (PV) panels generating up to 6.5 kW of electricity, and is heated by a 14-kW ground- source heat pump and occasionally by a wood stove. The floor area is
Contemporary offices
New office buildings are often hyped up as being amazingly environment-friendly. Let’s look at some numbers.
The William Gates building at Cambridge University holds computer science researchers, administrators, and a small café. Its area is
But are these buildings impressive? Next door, the Rutherford building, built in the 1970s without any fancy eco-claims – indeed without even double glazing – has a floor area of
Figure E.12: Building benchmarks. Power used per unit area in various homes and offices.
Figure E.13: Ideal heat pump efficiencies. Top left: ideal electrical energy required, according to the limits of thermodynamics, to pump heat out of a place at temperature Tin when the heat is being pumped to a place at temperature
Notice that the building power consumptions, per unit floor area, are in just the same units
Improving the coefficient of performance
You might think that the coefficient of performance of a condensing boiler, 90%, sounds pretty hard to beat. But it can be significantly improved upon, by heat pumps. Whereas the condensing boiler takes chemical energy and turns 90% of it into useful heat, the heat pump takes some electrical energy and uses it to move heat from one place to another (for example, from outside a building to inside). Usually the amount of useful heat delivered is much bigger than the amount of electricity used. A coefficient of performance of 3 or 4 is normal.
Theory of heat pumps
Here are the formulae for the ideal efficiency of a heat pump, that is, the electrical energy required per unit of heat pumped. If we are pumping heat from an outside place at temperature
If we are pumping heat out from a place at temperature
These theoretical limits could only be achieved by systems that pump heat infinitely slowly. Notice that the ideal efficiency is bigger, the closer the inside temperature
While in theory ground-source heat pumps might have better performance than air-source, because the ground temperature is usually closer than the air temperature to the indoor temperature, in practice an air-source heat pump might be the best and simplest choice. In cities, there may be uncertainty about the future effectiveness of ground-source heat pumps, because the more people use them in winter, the colder the ground gets; this thermal fly-tipping problem may also show up in the summer in cities where too many buildings use ground-source (or should I say “ground-sink”?) heat pumps for air-conditioning.
| Heat capacity: |
|
|---|---|
| Conductivity: |
|
| Density: |
|
| Heat capacity per unit volume: |
|
Vital statistics for granite. (I use granite as an example of a typical rock.)
Heating and the ground
Here’s an interesting calculation to do. Imagine having solar heating panels on your roof, and, whenever the water in the panels gets above
100 tonnes, which corresponds to a cuboid of rock of size
Ground storage without walls
OK, we’ve established the size of a useful ground store. But is it difficult to keep the heat in? Would you need to surround your rock cuboid with lots of insulation? It turns out that the ground itself is a pretty good insulator. A spike of heat put down a hole in the ground will spread as
| (W/m/K) | |
|---|---|
| water | 0.6 |
| quartz | 8 |
| granite | 2.1 |
| earth's crust | 1.7 |
| dry soil | 0.14 |
Thermal conductivities. For more data see table.
where
for example, after six months
Using the figures for water
So if the storage region is bigger than
Limits of ground-source heat pumps
The low thermal conductivity of the ground is a double-edged sword. Thanks to low conductivity, the ground holds heat well for a long time. But on the other hand, low conductivity means that it’s not easy to shove heat in and out of the ground rapidly. We now explore how the conductivity of the ground limits the use of ground-source heat pumps.
Consider a neighbourhood with quite a high population density. Can everyone use ground-source heat pumps, without using active summer replenishment (as discussed)? The concern is that if we all sucked heat from the ground at the same time, we might freeze the ground solid. I’m going to address this question by two calculations. First, I’ll work out the natural flux of energy in and out of the ground in summer and winter.
Figure E.16: The temperature in Cambridge, 2006, and a cartoon, which says the temperature is the sum of an annual sinusoidal variation between
If the flux we want to suck out of the ground in winter is much bigger than these natural fluxes then we know that our sucking is going to significantly alter ground temperatures, and may thus not be feasible. For this calculation, I’ll assume the ground just below the surface is held, by the combined influence of sun, air, cloud, and night sky, at a temperature that varies slowly up and down during the year (figure E.16).
Response to external temperature variations
Working out how the temperature inside the ground responds, and what the flux in or out is, requires some advanced mathematics, which I’ve cordoned off in box E.19.
The payoff from this calculation is a rather beautiful diagram (figure E.17) that shows how the temperature varies in time at each depth. This diagram shows the answer for any material in terms of the characteristic length-scale
Figure E.17: Temperature (in
For the case of daily variations and solid granite, the characteristic length-scale is
Let’s focus on annual variations and discuss a few other materials. Characteristic length-scales for various materials are in the third column of table. For damp sandy soils or concrete, the characteristic length- scale
The natural flux varies during the year and has a peak value (equation (E.9)) that is smaller, the smaller the conductivity.
For the case of solid granite, the peak flux is
What does this mean? I suggest we take a flux in the middle of these numbers,
The population density of a typical English suburb corresponds to
This is uncomfortably close to the sort of power we would like to deliver in winter-time: it’s plausible that our peak winter-time demand for hot air and hot water, in an old house like mine, might be 40 kWh/d per person.
This calculation suggests that in a typical suburban area, not everyone can use ground-source heat pumps, unless they are careful to actively dump heat back into the ground during the summer.
Let’s do a second calculation, working out how much power we could steadily suck from a ground loop at a depth of
|
thermal conductivity |
heat capacity |
length-scale |
flux |
|
|---|---|---|---|---|
| Air | 0.02 | 0.0012 | ||
| Water | 0.57 | 4.18 | 1.2 | 5.7 |
| Solid granite | 2.1 | 2.3 | 3.0 | 8.1 |
| Concrete | 1.28 | 1.94 | 2.6 | 5.8 |
| Sandy soil | ||||
| dry | 0.30 | 1.28 | 1.5 | 2.3 |
| 50% saturated | 1.80 | 2.12 | 2.9 | 7.2 |
| 100% saturated | 2.20 | 2.96 | 2.7 | 9.5 |
| Clay soil | ||||
| dry | 0.25 | 1.42 | 1.3 | 2.2 |
| 50% saturated | 1.18 | 2.25 | 2.3 | 6.0 |
| 100% saturated | 1.58 | 3.10 | 2.3 | 8.2 |
| Peat soil | ||||
| dry | 0.06 | 0.58 | 1.0 | 0.7 |
| 50% saturated | 0.29 | 2.31 | 1.1 | 3.0 |
| 100% saturated | 0.50 | 4.02 | 1.1 | 5.3 |
Thermal conductivity and heat capacity of various materials and soil types, and the deduced length-scale
If, as above, we assume a population density corresponding to
So again we come to the conclusion that in a typical suburban area composed of poorly insulated houses like mine, not everyone can use ground-source heat pumps, unless they are careful to actively dump heat back into the ground during the summer. And in cities with higher population density, ground-source heat pumps are unlikely to be viable.
I therefore suggest air-source heat pumps are the best heating choice for most people.
Thermal mass
Does increasing the thermal mass of a building help reduce its heating and cooling bills? It depends. The outdoor temperature can vary during the day by about
However, large thermal mass is not always a boon. If a room is occupied in winter for just a couple of hours a day (think of a lecture room for example), the energy cost of warming the room up to a comfortable temperature will be greater, the greater the room’s thermal mass. This extra invested heat will linger for longer in a thermally massive room, but if nobody is there to enjoy it, it’s wasted heat. So in the case of infrequently-used rooms it makes sense to aim for a structure with low thermal mass, and to warm that small mass rapidly when required.
Notes and further reading
Table. Sources: Bonan (2002),
www.hukseflux.com/thermalScience/thermalConductivity.html
If we assume the ground is made of solid homogenous material with conductivity
For a sinusoidal imposed temperature with frequency
the resulting temperature at depth
where
The flux of heat (the power per unit area) at depth
For example, at the surface, the peak flux is
Working out the natural flux caused by sinusoidal temperature variations.
| Color | Highlighted Text | Notes | |
|---|---|---|---|
| Please Sign In to create your own Highlights / Notes | |||
| Cover Image | Attributions |
|---|---|
| License: CC BY-NC |
Your search did not match anything in .